What are the MODBUS registers for Flow Totalization for the FL1500?

Dokument-ID

Dokument-ID TE8688

Veröffentlichungsdatum

Veröffentlichungsdatum 17.10.2017
Frage
What are the MODBUS registers for Flow Totalization for the FL1500?
Zusammenfassung
FL1500 MODBUS Flow Totalizer Registers
Antwort
 Tag Name  Register #    Data Type  Length  R/W   Description
 Flow Totalizer (Non-Resettable) – Sensor 1  40206   32-bit Float    2  R

 This register represents the non-resettable totalizer value for sensor 1. It returns value in single precision floating point.

 Flow Totalizer (Resettable) – Sensor 1

 40208

 32-bit Float

 2

 R

 This register represents the resettable totalizer value for sensor 1. It returns value in single precision floating point.

 Flow Totalizer (Non-Resettable) – Sensor 2

 40210

 32-bit Float

 2

 R

 This register represents the non-resettable totalizer value for sensor 2. It returns value in single precision floating point.

 Flow Totalizer (Resettable) – Sensor 2

 40212

 32-bit Float

 2

 R

 This register represents the resettable totalizer value for sensor 2. It returns value in single precision floating point.

 Flow Totalizer (Non-Resettable) – Sensor 3

 40214

 32-bit Float

 2

 R

 This register represents the non-resettable totalizer value for sensor 3. It returns value in single precision floating point.

 Flow Totalizer (Resettable) – Sensor 3

 40216

 32-bit Float

 2

 R

 This register represents the resettable totalizer value for sensor 3. It returns value in single precision floating point.

 Flow Totalizer (Non-Resettable) – Sensor 4

 40218

 32-bit Float

 2

 R

 This register represents the non-resettable totalizer value for sensor 4. It returns value in single precision floating point.

 Flow Totalizer (Resettable) – Sensor 4

 40220

 32-bit Float

 2

 R

 This register represents the resettable totalizer value for sensor 4. It returns value in single precision floating point.

 Flow Totalizer (Non-Resettable) – Internal AI

 40222

 32-bit Float

 2

 R

 This register represents the non-resettable totalizer value for internal AI. It returns value in single precision floating point.

 Flow Totalizer (Resettable) – Internal AI

 40224

 32-bit Float

 2

 R

 This register represents the resettable totalizer value for internal AI. It returns value in single precision floating point.

 Flow Totalizer (Non-Resettable) – External AI – A

 40226

 32-bit Float

 2

 R

 This register represents the non-resettable totalizer value for external AI - A. It returns value in single precision floating point.

 Flow Totalizer (Resettable) – External AI – A

 40228

 32-bit Float

 2

 R

 This register represents the resettable totalizer value for external AI - A. It returns value in single precision floating point.

 Flow Totalizer (Non-Resettable) – External AI – B

 40230

 32-bit Float

 2

 R

 This register represents the non-resettable totalizer value for external AI - B. It returns value in single precision floating point.

 Flow Totalizer (Resettable) – External AI – B

 40232

 32-bit Float

 2

 R

 This register represents the resettable totalizer value for external AI - B. It returns value in single precision floating point.