Application Note: WWTP Pilots Ammonia-Based Aeration Control with Hach RTC-N to Optimize Nitrification

Dokument-ID

Dokument-ID CO301

Veröffentlichungsdatum

Veröffentlichungsdatum 12.05.2022
Frage
Application Note: WWTP Pilots Ammonia-Based Aeration Control with Hach RTC-N to Optimize Nitrification
Zusammenfassung
The diurnal ammonia loading fluctuates between 40.6 to 88.6 lbs/hr. To maximize nitrification, the DO concentration in the aeration basin trains is kept higher than necessary during most of the day in anticipation of increased load.
Antwort
This plant, in San Bernardino, California, installed the Hach® Real-Time Control System for Nitrification, at one of the plant’s six aeration basin trains to measure ammonia and calculate the optimal DO setpoint in real-time. This would allow operators to gain insight into their process continuously instead of using discrete grab sample data points.

Real-time nitrification measurement allows the facility to lower DO to achieve ammonia effluent values of zero during the lower load periods. Also, it’s possible during high load periods to reduce inflow and maintain loading levels using existing equalization basins. This ensures compliance and opens the possibility for lower aeration energy costs.

WWTP Pilots Ammonia-Based Aeration Control with Hach RTC-N to Optimize Nitrification_DOC043.53.30384
 